apcupsd
- -
- -- - - - -
# systemctl status apcupsd | |
# systemctl restart apcupsd | |
# systemctl status apcupsd | |
# apcaccess status | root@APC-900-mgmt:~# apcaccess status APC : 001,036,0880 DATE : 2019-05-20 19:56:01 +0200 HOSTNAME : APC-900-mgmt VERSION : 3.14.14 (31 May 2016) debian UPSNAME : APC-900-mgmt CABLE : USB Cable DRIVER : USB UPS Driver UPSMODE : Stand Alone STARTTIME: 2019-05-20 19:54:13 +0200 MODEL : Back-UPS RS 900G STATUS : ONLINE LOWBATT LINEV : 235.0 Volts LOADPCT : 25.0 Percent BCHARGE : 13.0 Percent TIMELEFT : 0.2 Minutes MBATTCHG : 5 Percent MINTIMEL : 3 Minutes MAXTIME : 0 Seconds SENSE : Medium LOTRANS : 176.0 Volts HITRANS : 294.0 Volts ALARMDEL : No alarm BATTV : 27.1 Volts LASTXFER : No transfers since turnon NUMXFERS : 0 TONBATT : 0 Seconds CUMONBATT: 0 Seconds XOFFBATT : N/A SELFTEST : NO STATFLAG : 0x05000048 SERIALNO : 3B1402X00102 BATTDATE : 2014-01-06 NOMINV : 230 Volts NOMBATTV : 24.0 Volts NOMPOWER : 540 Watts FIRMWARE : 879.L4 .I USB FW:L4 END APC : 2019-05-20 19:56:03 +0200 |
# systemctl stop apcupsd | |
# apctest | 2 = Perform self-test |
Select function number: 2 This test instructs the UPS to perform a self-test operation and reports the result when the test completes. Clearing previous self test result...CLEARED Initiating self test...INITIATED Waiting for test to complete...TEST DID NOT COMPLETE |
|
10) Perform battery calibration | |
- -- - - - -